TFR-8 0.6/1kV

Products

TFR-8 2x 4mm²

Nexans ref. 84003349

  • Number of cores: 2
  • Conductor cross-section: 4 mm²
  • Approximate weight: 210 kg/km

TFR-8 4x 1.5mm²

Nexans ref.

  • Number of cores: 4
  • Conductor cross-section: 1.5 mm²
  • Approximate weight: 200 kg/km

Description

Description

Standards

  • International
    Nexans specification
  • National
    KS C IEC 60502-1

Application

Power cable for residential, commercial building and distribution circuit.
The flame retardant cable for tray conformed to the standard of technique of electrical equipment.

 

Standard

K 60502-1

Nexans standard

 

Construction

1. Conductor: Annealed copper stranded conductor, Class 2

2. Fire resistant Mica tape.

3. Insulation: Cross-linked polyethylene (XLPE), Max operating temperature: 90°C.

4. Unit: Cabling circularly insulated solid wire in case of more 2 cores

5. Outer sheath: Black flame retardant PVC (TFR-PVC)

 

Colors

1 core: Natural color
2 cores: White, Black
3 cores: White, Black, Red
4 cores: White, Back, Red, Green

 

Certification

KETI (Safety certification for electrical products)

TFR-8 0.6/1kV design

##image:56140##

Conductor 

Mica tape 

Insulation 

Filler 

Binder tape 

Outer sheath (TFR PVC)

 

The values of insulation resistance is not defined but only constant number of insulation resistance is defined.
(K=min. 36.7MΩ.km at 90℃)

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Annealed copper
Type of conductor
Stranded, Class 2
Insulation
Micatape + XLPE
Outer sheath
PVC

Dimensional characteristics

Dimensional characteristics

Outer Diameter
16 mm

Electrical characteristics

Electrical characteristics

Test voltage
3500 V
Rated Voltage Uo/U (Um)
0.6/1 kV

Usage characteristics

Usage characteristics

Operating temperature, range
-15 - 60 °C
Flame retardant
KSC IEC 60332-3
Bending factor when installed
12 (xD)

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.